| SYSTEM OVERVIEW |
System overview: |
Standby tower UPS protects PCs and network workstations from blackouts, surges and line noise. Maintains AC output during blackouts and brownouts starting at 99V. Includes front panel LED indicators. |
Voltage compatibility: |
120V AC |
Frequency compatibility: |
60Hz |
| OUTPUT |
Output volt amp capacity (VA): |
450 |
Output watt capacity (watts): |
280 |
Output nominal voltage: |
120V AC |
Output frequency regulation: |
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz |
Outlet quantity / type: |
3 NEMA 5-15R |
| INPUT |
|
Input connection type: |
NEMA 5-15P |
Input cord length: |
6 ft., 18 gauge |
Recommended electrical service: |
15A 120V |
| BATTERY |
Full load runtime: |
5 minutes (450VA) |
Half load runtime: |
17 minutes (225VA) |
DC system voltage: |
12 VDC |
Typical battery lifespan: |
3-6 years, depending on usage |
Battery recharge rate: |
2-4 hours to 90% |
Replacement Battery Cartridge: |
RBC51 |
| LEDS ALARMS & SWITCHES |
Front panel LEDs: |
3 front panel LEDs indicate line power status, battery power status and battery low/replace status |
Alarms: |
Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain. |
Switches: |
Includes 2 front panel switches—one main on/off power switch and one dual function "alarm cancel" / "self test" button |
| SURGE / NOISE SUPPRESSION |
AC surge suppression: |
400 joules |
AC suppression response time: |
Instantaneous |
Dataline suppression: |
- |
EMI / RFI AC noise suppression: |
Yes |
| PHYSICAL |
Shipping weight (lbs): |
15 |
Shipping weight (kg): |
6.8 |
Unit weight (lbs): |
14.4 |
Unit weight (kg): |
6.5 |
Unit Dimensions (HWD/in): |
8.75 x 5.25 x 6.75 |
Unit Dimensions (HWD/cm): |
22.2 x 13.3 x 17.1 |
Material of construction: |
PVC |
Form factors supported: |
Tower |
Cooling method: |
Convection |
Battery Access: |
Battery access door allows user replacement of UPS batteries. Hot-swappable battery replacement supported. |
| ENVIRONMENTAL |
Operating Temperature: |
+32 to +104 degrees Fahrenheit 0 to +40 degrees Celsius |
Storage Temperature: |
+5 to +122 degrees Fahrenheit -15 to +50 degrees Celsius |
Relative Humidity: |
0 to 95%, non-condensing |
| COMMUNICATIONS |
Network monitoring port: |
- |
| LINE / BATTERY TRANSFER |
Transfer time from line power to battery mode: |
2-4 milliseconds |
Low voltage transfer to battery power: |
Switches to battery power as line voltage decreases to 99 volts or less. Resets to line power mode as line voltage increases to 104V or higher |
High voltage transfer to battery power: |
Yes |
| CERTIFICATIONS |
Certifications: |
UL1778 (USA), cUL (Canada), FCC Class B (emissions), NOM (Mexico) |
| WARRANTY |
Optional coverage: |
3-5 year warranties, plus next day and on-site warranty coverage available. Contact Tripp Lite for additional information. |
Product warranty: |
2 year product warranty |
Connected equipment insurance (USA and Canada Only): |
$100,000 connected equipment insurance (USA and Canada only) |
| SPECIAL FEATURES |
Cold Start: |
Yes, inverter can be "cold started" to enable temporary AC output during a power failure |
Appearance: |
Attractive gray tower UPS |